Power duct for smart city
Sudarshan Power Ducts, manufactured to the international ASTMF 2160 standard, feature a robust three-layer silicone-coated structure with inner ribbing, designed to protect high voltage cables over the long term. Widely used in smart city projects like Amaravati in Andhra Pradesh, these ducts ensure safety, reliability, and easy traceability of critical power infrastructure. Available in coil form in sizes ranging from 50 mm to 75 mm, and in standard lengths of 6 to 9 meters for sizes 90 mm to 160 mm, they offer versatile solutions for modern electrical and telecommunications networks.

Specifications

S. No.
PARTICULAR
DETAIL
1
Sam le Size -
5Mtr * 3Duct + 1.5Mtr*3 Duct
2
Grade variety/type/size/class
HDPE PLB DUCT 40mm/33mm
3
Batch Number
202406260091
4
Marking on pipe
SUDARSHAN HDPE PLB DUCT PIPE 50mm/42mm 006 220521
5
Raw Material Used
PE-63 , Blue Master Batch, Silicon, White Master Batch, UV Master batch
6
Date of initiation
01.07.2024
7
Date of Completion
10.07.2024
8
An Other Information
Colour Of Duct-Blue

GEOMETRICAL CHARACTERISTICS & DIMENSIONS OF PIPE

S. No.
Characteristic
Unit
Test Cl. No.
Test Method
Specified Requirement
Observed Value
1
Visual Appearance
Table-3
TEC/GR/FNCDS - 008/04/AUG-19
The internal & External-surface of the pipe shall be smooth, clean & free from oovin & other defects.
Satisfactory
2
Length of Duct/Coil
M tr
4.3 Table3
TEC/GR/FA/CDS -008/04/AUG-19
3
Colour of Duct
4.2.1
TEC/GR/FA/CDS -008/04/AUG-19
Shall be Blue
Blue
4
Colour of Inner Layer
4.2.7
TEC/GR/FA/CDS -008/04/AUG-19
Shall be White
White
5
Colour of Strip
424
TEC/GR/FA/CDS -008/04/AUG-19
Approximately 4
4
6
No. Of Strip
Numbers
4 2.3
TEC/GR/FA/CDS -008/04/AUG-19
Approximately 4
4
7
Width Of strip
mm
42.3
TEC/GR/FA/CDS -008/04/AUG-19
Min. 3.0
3.15
8
Outside Diameter
mm
4.3 Table3
TEC/GR/FA/CDS -008/04/AUG-19
Min. 40.00 / Max. 40 40
40.10 / 40.25
9
Inner Layer Thickness
mm
4.3 Table3
TEC/GR/FA/CDS -008/04/AUG-19
Min. 0.28 / Max. 0.42
0.34 / 0.39
10
Ovality
mm
Table-4
TEC/GR/FA/CDS -008/04/AUG-19
Max. 1.4
055
11
Wall Thickness
mm
mm4.3 Table3
TEC/GR/FA/CDS -008/04/AUG-19
Min. 3.3 / Max. 35
3 38 / 345
12
Maximum outer diameter of 'cal Fibre cable
mm
4.3 Table3
TEC/GR/FA/CDS -008/04/AUG-19
Max. 16 mm

Test Result as per GR No : TEC/GWFA/CDS-008/04/AUG-19

PERFORMANCE REQUIREMENTS

S. No.
Parameter
Unit
Test Cl. No.
Test Method
Specified Requirement
Observed Value
Remark
Il draulic Characteristics Of Duct
Internal Pressure creep rupture test:
a
Test Duratton.48hr Test Temp-800C
8.1 1, Table-5 Of 4984 2016
IS-4984 2016 & Table-5 or TEC/GWFA/CDS008/04/AUG-19
Pipe shall show no Sign of localized swelling leakage or weeping and shall not burst durtng prescribed test duration (Induced Stress as per Table-5 Of TEC/GWFAJCDS-OOW04/AUG-19
No sign of failure Confirmed
Result Pass/fail
b
Test Duration- 165hr Test Temp.800C
81 1. Table-5 Of 4984 2016
IS-4984 2016 & Table-5 or TEC/GWFA/CDS008/04/AUG-19
Pipe shall show no Sign of localized swelling leakage or weeping and shall not burst during prescribed test duration (Induced Stress as per Table-5 or TEC/GWFA/CDS-008/04/AUG-19
No Sign of failure Confirmed
Result Pass/fail
2. Acceptance Test On Duct
a
Optional pre-installed
TEC/GWFA/CDS008/04/AUG-19
Duct sue -32,Q6mm, 40/33mm SO/42mm requirement -4mm dta ,2% slackness Duct Stze-63/50mm , 110/80mm utrement-6mm dia
b
Tensile Strength & Elongation
N/mm2
ASTM F2160 & ASTM 638
Tensile strength at yield —run-20N/mm2 Elongation — Min-500%
>23.5N/mm2 > 907 4%
c
Longitudinal Reversion Test
8 2 Annex
IS-4984 2016
Shall not change more than 3% in the longitudinal direction
Max-2 05
d
Environmental Stress Crack Resistance
ASTM -1693
There shall be no failure/crack
No Crack Observed - Pass, ‘fail
IGEPAL
e
Impact Strength
IS-12235 . Pt-9
The duct shall not crack or split
No crack observed
Result- Pass/fail
f
Crush Resistant
TEC/GWFAiCDS008/04/AUG-19
The deflecuon With load on and after recovery penod(5min) shall not exceed & 2% Respectively
Deflection with loadDeflection after recovery penod
g
Mandrel Test
CL-4 10
TEC/GR,'FA/CDS008/04/AUG-19
150mm long mandrel of dia 3mm less than the Internal dia of duct shall be passed through a 5meter length of Duct freely throughout the length, when the duct IS bent to a radius of 5Meter
Satisfactory
Result Pass/fail
h
Coil set
When a nummum length of 50 meters Duct taken from the coil and laid on the ground , It shall be straight without any bends or kinks and Without deformation ex 5meter from each end
Satisfactory
i
Wall ThicknesOxidation Induction Test s
M in
4.13 , Annex- I
TEC/GWFA/CDS008/04/AUG-19
Shall not Less Than 30 Minute
26
DSC Result
j
Internal Co-efficient of fnctvon
4 15, Annex-2
TEC/GWFA/CDS008/04/AUG-19
a) For Nylon Jacketed unarmoured OFC • 006 Max For HDPE PLB Ducts
b) For HDPE Jacketed Unarmoured OFC 020Max For HDPE PLB Ducts
0.168
(For HDPE Jacketed Unarmoure d OFC
k
Optical Fibre Cable blow Ing test
4 17
TEC/GWFA,'CDS008/04/AUG-19
It shall Possible to blow in the Optical through the I km duct each time tn not more than 35min